The universal PV inverter with maximum yield.

Maximum power:
This three power stage inverter is available in 10.0, 11.4 and 12.0 kW in single and three-phase applications.  Best suited for large residential and commercial applications.

 

Available IG Plus / IG Plus V Three Stage Inverters:

10.0-1 UNI
11.4-1 UNI
10.0-3 Delta
11.4-3 Delta
12.0-3 WYE277

 

Technical Data


Fronius IG Plus
10.0-1UNI 11.4-1UNI 11.4-3Delta 12.0-3WYE277
Input data
       
Recommended PV-Power (kWp) 8.5-11.5 9.7-13.1 9.7-13.1 10.2-13.8
MPPT-Voltage range 230 - 500 V
Max. Input voltage range
(at 1000 W/m² 14°F (-10°C) in open circuit operation)
600 V
Nominal Input Current 27.6 A 31.4 A 31.4 A 33.1 A
Max. usable Input Current 46.7 A 53.3 A 53.3 A 56.1 A
Admissible conductor size (DC) No. 14-6 AWG
 
Output data
       
Nominal output power (PAC nom)  9995 W  11400 W  11400 W  12000 W
Max. continupous output power
104°F (40°C) 208 V / 240 V /
277 V
 9995 W  11400 W  11400 W  12000 W
Nominal AC output voltage  208 V / 240 V / 277 V  208 V / 240 V  277 V
Operating AC voltage range (default)
208 V
240 V
277 V

183 - 229 V (-12 / +10 %)
211 - 264 V (-12 / +10 %)
244 - 305 V (-12 / +10 %)




Maximum continuous output current
208 V
240 V
277 V

48.1 A
41.7 A
36.1 A

54.8 A
47.5 A
41.2 A

31.6 A*
27.4 A*
n.a.

n.a.
n.a.
14.4 A*
Admissible conductor size (AC)  No. 14 - 4 AWG
Max. continuous utility back feed current  0 a
Nominal frequency  60 Hz
Operating frequency range  59.3 - 60.5 Hz
Total harmonic distortion  < 3 %
Power factor  1
 
General data
       
Max. Efficiency 96.2 %
CEC Efficiency
208 V
240 V
277 V

95.0 %
95.5 %
96.0 %

95.5 %
96.0 %
96.0 %

95.0 %
95.5 %
n.a.

n.a.
n.a.
96.0 %
Consumption in standby (night) < 1 W
Consumption during operation 22 W
Cooling Controlled forced ventilation, variable speed fan
Enclosure Type NEMA 3R
Unit Dimensions (W x H x D) 17.1 x 48.1 x 9.6. in. 
Power Stage Weight 82 lbs. (37 kg)
Wiring Compartment Weight 26 lbs. (12 kg)
Admissing ambient operating temperature -13 ... 131°F (-25 ... + 55°C)
Compliance UL 1741-2005, IEEE1547-2003, IEEE 1547.1, ANSI/IEEE C62.41,
FCC Part 15 A&B, NEC Article 690, C22. 2 No. 107.1-01
(Sept. 2001)
 
Safety equipment
       
Ground fault protextion  Internal GFDI (Ground Fault Detector/Interrupter); in accordance with UL 1741-2005 and NEC Art. 690
DC reverse polarity protevtion  Internal diode
Islanding protection Internal; in accordance with UL 1741-2005, IEEE 1547-2003 and NEC
Over temperature Output power derating / active cooling
 
* per Phase   The right to make technical modifications is reserved.

Fronius IG Plus V
10.0-1UNI 11.4-1UNI 10.0-3Delta 11.4-3Delta 12.0-3WYE277
Input data
         
Recommended PV-Power (kWp) 8.5-11.5 9.7-13.1 8.5-11.5 9.7-13.1 10.2-13.8
MPPT-Voltage range 230 - 500 V
Max. Input voltage range
(at 1000 W/m² 14°F (-10°C) in open circuit operation)
600 V
Nominal Input Current 27.6 A 31.4 A 27.6 A 31.4 A 33.1 A
Max. usable Input Current 46.7 A 53.3 A 46.7 A 53.3 A 56.1 A
Admissible conductor size (DC) No. 14-6 AWG
 
Output data
         
Nominal output power (PAC nom)  9995 W  11400 W  9995 W  11400 W  12000 W
Max. continupous output power
104°F (40°C) 208 V / 240 V /
277 V
 9995 W  11400 W  9995 W  11400 W  12000 W
Nominal AC output voltage  208 V / 240 V / 277 V  208 V / 240 V  277 V
Operating AC voltage range (default)
208 V
240 V
277 V

183 - 229 V (-12 / +10 %)
211 - 264 V (-12 / +10 %)
244 - 305 V (-12 / +10 %)





Maximum continuous output current
208 V
240 V
277 V

48.1 A
41.7 A
36.1 A

54.8 A
47.5 A
41.2 A

27.7 A*
24.0 A*
n.a.

31.6 A*
27.4 A*
n.a.

n.a.
n.a.
14.4 A*
Admissible conductor size (AC)  No. 14 - 4 AWG
Max. continuous utility back feed current  0 a
Nominal frequency  60 Hz
Operating frequency range  59.3 - 60.5 Hz
Total harmonic distortion  < 3 %
Power factor  1
 
General data
         
Max. Efficiency 96.2 %
CEC Efficiency
208 V
240 V
277 V

95.0 %
95.5 %
96.0 %

95.0 %
95.5 %
96.0 %

95.0 %
96.0 %
n.a.

95.0 %
96.0 %
n.a.

n.a.
n.a.
96.0 %
Consumption in standby (night) < 1.5 W
Consumption during operation 20 W
Cooling Controlled forced ventilation, variable speed fan
Enclosure Type NEMA 3R
Unit Dimensions (W x H x D) 17.1 x 49.7 x 9.9. in. 
Power Stage Weight 84 lbs. (38 kg)
Wiring Compartment Weight 26 lbs. (12 kg)
Admissing ambient operating temperature -13... 131°F (-25 ... + 55°C)
Compliance UL 1741-2005, IEEE1547-2003, IEEE 1547.1, ANSI/IEEE C62.41,
FCC Part 15 A&B, NEC Article 690, C22. 2 No. 107.1-01
(Sept. 2001), California Solar Initiative - Program Handbook - Appendix C: Inverter Integral 5 % Meter Performance Specification
 
Safety equipment
         
Ground fault protection  Internal GFDI (Ground Fault Detector/Interrupter); in accordance with UL 1741-2005 and NEC Art. 690
DC reverse polarity protevtion  Internal diode
Islanding protection Internal; in accordance with UL 1741-2005, IEEE 1547-2003 and NEC
Over temperature Output power derating / active cooling
 
* per Phase   The right to make technical modifications is reserved.

Equipment features


Grounding selectable on site.
Decide on site what type of grounding is required as the Fronius IG Plus is field programmable for either positive or negative module grounding.
 
Designed for indoor and outdoor installations.
All Fronius IG Plus inverters have a robust, well designed aluminum housing.  UV resistance and corrosion protection enable them to be used either indoors or outdoors.  Fronius is proud to be one of the only inverters tested and approved to operate at 122
 
Integrated DC disconnect.
No external DC disconnect installation or cabling is necessary.  The Fronius IG Plus comes complete with an approved, built-in, lockable and load breakable DC Disconnect.
 
The new power plug system.
The connection area and power stages are installed separately from each other. Very easy and extremely safe:  The connection area is attached to the wall as normal. Then the power module is simply plugged in. The power plug connects both parts into one secure unit.  If service is required, the connector remains on the wall  maintaining all settings and configurations.
 
Field Programmable AC output voltage.
The Fronius IG Plus inverter line from 3.0 to 11.4 kW is field programmable to 208, 240 or 277 volts (Fronius IG Plus 12.0 kW only availabale in 277 volts), eliminating the need to install different inverter models to accommodate three-phase installations.
 
 

Technology


FRONIUS MIX TECHNOLOGY
/ The clever combination of multiple power stages means Fronius inverters always achieve maximum yield, even with partial-loads. This is due to the unique Fronius Master Inverter X-Change system (MIX), a development of the classic master/slave principle. How it works: All power stages are equal. The “master” is allocated alternately, depending on the operating hours. The result is that loads are applied evenly to individual power stages decreasing operating time on any one power stage.
/ Maximum efficiency under partial load
With MIX technology, get the maximum power harvest out of partial load ranges, e.g. on cloudy days, through a clever combination of multiple power stages in each inverter. The power stages in Fronius inverters divide up the work depending on operating hours and only operate as many power stages as required to efficiently process available power from the PV array.
/ Unrivalled stability
The redundant design means that even if one power stage fails the inverter continues to operate, ensuring yields are achieved. In the unlikely event a power stage fails the others will continue to operate.
/ Longer service life
Depending on the operation hours of each power stage, our inverters decide which power stages run under partial load conditions. This ensures that the work load is distributed equally between the power stages. The result is reduced operating time of individual power stages which increases the lifespan of the inverter.


AUTOMATIC HF TRANSFORMER SWITCHING
/ Fronius transformer inverters use a high-frequency (HF) transformer. The automatic transformer switching function produces three efficiency peaks. The result: A constant level of efficiency across the entire input voltage range, resulting in higher yields. Other key advantages of HF transformer technology are a compact, lightweight design, and safety as a result of the galvanic isolation.

FRONIUS MODULE MANAGER
/ The Fronius Module Manager always locates the maximum power point (MPP), even in the case of more demanding thin-film modules. The Fronius Module Manager achieves an outstanding MPP adaptation efficiency of >99.9 % in total.

UNIQUE PC BOARD REPLACEMENT PROGRAM
/ The foundation of our unique on-site PC board replacement program is laid as we develop our inverters, as PC boards can only be replaced if the device has been designed accordingly.  This enables our Authorized Service Provider to offer the fastest inverter servicing on the market.

QUICK MOUNTING SYSTEM
/ What is special about the design of our devices is the power plug system. The connection area and power stages are installed separately from each other. Very easy, and extremely safe: The connection area is attached to the wall as normal. Then the power stage is simply plugged in. The power plug connects both parts into one secure unit. If service is required, the connection area remains on the wall, maintaining all settings and configurations.

SMART VENTILATION DESIGN
/ With Fronius smart ventilation design, the air required for cooling is drawn through a closed channel over the heat sink. This prevents contact between outside air and the circuit boards while cooling the inverter components ensuring the inverter operates consistently. All circuit boards are also dipped in conformal coating to provide an added measure of protection.