The own solar powerstation
The Fronius IG central inverters are suitable for pv systems starting with an AC output power of 24 kW and work with a completely new system configuration. There is not only one power stack converting the electricity but also 9, 12 to 15 printed circuit boards that share the work, depending on the output class.
The Fronius IG central inverters are suitable for pv systems starting with an AC output power of 24 kW and work with a completely new system configuration. There is not only one power stack converting the electricity but also 9, 12 to 15 printed circuit boards that share the work, depending on the output class.
The reason for this is that it is well-known that the energy yield increases in part-load areas if smaller power stacks are operated at higher capacity. Therefore, every Fronius IG central inverter works with several smaller power stacks that switch on or off completely automatically depending on irradiance so that they can always deliver maximum power.
Technical Data
|
Fronius IG |
300 |
400 |
500 |
|---|---|---|---|
|
Input Data |
|||
| MPP voltage range | 210 - 420 V | 210 - 420 V | 210 - 420 V |
| Max. input voltage (at 1000 W/m²; - 10° C) | 530 V | 530 V | 530 V |
| Recommended PV plant output | 24 - 31 kWp | 32 - 42 kWp | 40 - 52 kWp |
| Max. input current | 123 A | 164 A | 205 A |
|
Output Data |
|||
| Nominal output | 24 kW | 32 kW | 40 kW |
| Max. power output | 24 kW | 32 kW | 40 kW |
| Max. efficiency | 94,3 % | 94,3 % | 94,3 % |
| Euro efficiency | 93,3 % | 93,4 % | 93,5 % |
| Mains voltage / frequency | 3NPE~400 V / 50 Hz | ||
| Distortion factor | < 5 % | ||
| Power factor | 1 | ||
| Power consumption at night | 9 W | ||
|
General Data |
|||
|
Size l x w x h; |
600 x 600 x 2557 mm | ||
| Size l x w x h; IP 43 incl. socket |
1112,5 x 600 x 2444,5 mm | ||
| Weight | 225 kg | 254 kg | 265 kg |
| Cooling | controlled forced-air cooling | ||
| Protection class (housing) | IP 20 (IP 43) | ||
| Ambient temperature range | - 20° C to 50° C | ||
| Permissible humidity | 0 to 95 % | ||
|
Protective Devices |
|||
| DC insulation measurement | warning when Riso < 500 k Ohm | ||
| Behaviour on DC overload | displacement of operating point | ||
Equipment features
- Fronius LC-Display
- HF-Transformer
- Module-Manager
- MIX-Concept
We recommend to use a Fronius String Control for monitoring the high number of module strings in a pv-system with Fronius IG Central inverters.
en