Technical Data
Input Data
Number of MPP trackers | 2 |
---|---|
Max. usable input current | NA |
Max. usable input current total (MPPT1 + MPPT2) | 51 A |
Max. array short circuit current (1.5 * Imax) | 76,5 A |
DC input voltage range (Udc min - Udc max) | 200-1000 V |
MPP Voltage Range | 450-800 V |
Max. input voltage (Udc max) | 1000 V |
Output Data
Max. output power 480 V | 20 kW |
---|---|
Max. output power 277 V | 20 kW |
Max. output power 240 V | NA |
Max. output power 208 V | NA |
Output configuration | 3~ NPE 480 V |
Frequency range | 50-66 Hz |
Frequency | 60 Hz |
Power factor range | 0-1 ind./cap. |
Max continuous output current 480 V | 24 A |
Max. continuous output current 277 V | 24 A |
Max. continuous output current 240 V | NA |
Max. continuous output current 208 V | NA |
General Data
Dimension / width | 511 mm |
---|---|
Dimension / height | 724 mm |
Dimension / depth | 226 mm |
Weight | 43,4 kg |
Installation | Indoor and outdoor installation, tilt from 0 - 90 degree (Fronius Shade Cover required for installation angles less than 15 degrees) |
Permitted humidity | 0 - 100 % (non-condensing) |
Degree of protection | NEMA 4X |
Night-time consumption | <1 W |
Inverter design | Transformerless |
Cooling | Variable speed fan |
Ambient Temperature Range | -40°F - + 140°F (-40°C - +60°C) |
Max. altitude | 2000 m (6562 ft) with a max. input voltage of 1000 V / 3400 m (11155 ft) with a max. input voltage of 850 V |
Certificates and compliance with standards | UL 1741-2010 Second Edition (incl. UL1741 Supplement SA 2016-09 for California Rule 21), UL1998 (for functions: AFCI, RCMU and isolation monitoring), IEEE 1547-2003, IEEE 1547a-2014, IEEE 1547.1-2003, ANSI/IEEE C62.41, FCC Part 15 A & B, NEC 2017 Article 690, C22. 2 No. 107.1-16, UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013 |
DC connection technology | 6x DC+ and 6x DC- screw terminals for copper (solid / stranded / fine stranded) or aluminum (solid / stranded) |
AC connection technology | Screw terminals 14-6 AWG |
Interference emission class | B |
Protection Devices
DC reverse polarity protection | Yes |
---|---|
Anti islanding | internal in accordance with UL 1741-2010, IEEE 1547-2003 and NEC |
Over temperature protection | Ouput power derating/Active cooling |
AFCI | Yes |
Rapid shutdown compliant | Yes |
Ground fault protection with isolation monitor interrupter | Yes |
DC disconnector | Yes |
Interfaces
Compatible Module Level Electronic | Tigo TS4-F based on SunSpec PLC (pending testing) |
---|---|
Power Line Communication (PLC) | Yes – SunSpec Rapid Shutdown communication standard |
USB (type A socket) | Datalogging and inverter update possible via USB |
2x RS422 (RJ45 socket) | Fronius Solar Net, interface protocol |
Wi-Fi / Ethernet / Serial / Datalogger and webserver | Wireless standard 802.11 b/g/n / Fronius Solar.web, SunSpec Modbus TCP, JSON / SunSpec Modbus RTU |
6 inputs and 4 digital I/Os | Load management signaling, multipurpose I/O |