Input Data
| Number of MPP trackers | 2 |
|---|---|
| Maximum PV input power | 5200 W |
Max. input current (Idc max) | 12,5 A / 12,5 A |
Max. short circuit current, module array* | 20,0 A / 20,0 A |
DC input voltage range (Udc min - Udc max) | 80-1000 V |
Feed-in start voltage (Udc start) | 80 V |
Nominal input voltage (Udc,r) | 610 V |
MPP voltage range (Umpp min - Umpp max) | 210-800 V |
| Usable MPP voltage range | 80-800 V |
| Number of DC connections | 2+1 |
Max. PV generator power (Pdc max) | 7,5 kWpeak |
Output Data
AC nominal output (Pac,r) | 5000 W |
|---|---|
Max. output power (Pac max) | 5000 VA |
| Max. grid power demand | 10 VA |
| Max. AC output current | 8 A |
Grid connection (Uac,r) | 3~NPE 230V / 400V, 3~NPE 220V / 380V |
AC voltage range (Umin - Umax) | 154-280 V |
Frequency (fr) | 50 / 60 Hz |
Frequency range (fmin - fmax) | 45-66 Hz |
Power factor (cos φac,r) | 0,7 - 1 ind./cap. |
| Back-up power | 1 ~ NPE 220 V / 230 V |
| Nominal AC output current (380VAC) | 7,6 A |
| Nominal AC output current (400VAC) | 7,2 A |
Output Data PV Point
| Max continuous output power | 3000 VA |
|---|---|
Nom. output current (Iac max) | 13 A |
| Grid connection | 1 ~ NPE 220 V / 230 V |
| Frequency | 50 Hz / 60 Hz |
| Max. switchover time PV-Point | 15 s |
| Max. switchover time Full Backup | 10 s |
| Frequency in backup power mode | 53 Hz |
Battery Connection
| Number of DC connections | 1 |
|---|---|
Max. input current (Idc max.) | 12,5 A |
| Max. input / output power (Depending on the connected battery) | 5200 W |
| Min. DC input voltage Battery input | 160 V |
| Max. DC input voltage Battery input | 700 V |
General Data
| Dimension / length | 165 mm |
|---|---|
| Dimension / width | 474 mm |
| Dimension / height | 530 mm |
| Dimension / depth | 165 mm |
| Weight | 15,61 kg |
| Weight incl. packaging | 19,35 kg |
| Degree of protection | IP66 |
| Protection class | 1 |
Overvoltage category (DC / AC) 1) | 2/3 |
| Night-time consumption | <10 W |
| Inverter design | Transformerless |
| Cooling | Regulated air cooling |
| Installation | Indoor and outdoor installation |
| Ambient temperature range | -25 - +60°C |
| Permitted humidity | 0 - 100% |
| Max. altitude | 3000m / 4000m |
Max. altitude 2) | 4000 m |
| DC PV connection technology | 3x DC+ and 3x DC- push-in spring terminals 2.5 - 10 mm² |
| DC battery connection technology | 1x BATT+ and 1x BATT- push-in spring terminals 2.5 - 10 mm² |
| AC connection technology | 5 pole AC push-in spring terminals 1.5 - 10 mm² 3 pole backup power push-in spring terminals 1.5mm² - 10mm² 5x PE-screw terminals 2.5 - 16 mm² |
| Certificates and compliance with standards | IEC 62109, IEC 62116, IEC 61727, IEC 62909, VDE 0126, VDE AR-N4105, AS/NZS 4777.2, EN 50549, CEI 0-21, G 98, R25 6) |
| Back-up power functions | PV Point |
| Sound emissions | 36 dB(A) |
| Interference emission class | B |
Compatible batteries 5) | BYD Battery-Box Premium HVS/HVM 4) & LG FLEX |
Efficiency
| Max. efficiency (PV - grid) | 98,2 % |
|---|---|
| European efficiency (ηEU) | 97.5% |
η at 5% Pac,r 3) | 91.2% |
η at 10% Pac,r 3) | 94.9% |
η at 20% Pac,r 3) | 96.9% |
η at 25% Pac,r 3) | 97.3% |
η at 30% Pac,r 3) | 97.5% |
η at 50% Pac,r 3) | 98.0% |
η at 75% Pac,r 3) | 98.1% |
η at 100% Pac,r 3) | 98.2% |
| MPP adaptation efficiency | 99.9% |
Protection Devices
| DC insulation measurement | Yes |
|---|---|
| Overload behaviour | Operating point shift. Power limitation |
| DC disconnector | Yes |
| DC Reverse polarity protection | Yes |
Interfaces
| WLAN / 2x Ethernet LAN | Fronius Solar.web, Modbus TCP SunSpec, Fronius Solar API (JSON) |
|---|---|
| 6x digital in/out + 6x digital in | Interface to ripple control receiver, energy management |
| Emergency stop (WSD) | Yes |
| Datalogger and web server | Included |
| 2x RS485 | Modbus RTU SunSpec (third-party supplier) / Fronius Smart Meter, battery, Fronius Ohmpilot |
More information about the features of this product
Clear HTML version of the operating instructions. Mobile and optimised for every device.
Information for installation and commissioning
Downloads
Show all downloads for product
Footnotes for technical data
1) According to IEC 62109-1. Option to retrofit surge protection device DC SPD type 1+2 for 2 MPP trackers available under the following item number: 4,240,313,CK
2) Unrestricted / restricted voltage range.
3) At Udc,r
4) This does not apply to the BYD Battery-Box Premium HVS 12.8 & HVM 8.3
5) Depending on the country-specific certification and availability
6) You can find the current certificates under www.fronius.com/symo-gen24-plus-cert
* Isc pv = Isc max ≥ Isc (STC) x 1,25 according to e.g..: IEC 60364-7-712, NEC 2020, AS/NZS 5033:2021.