Technical Data

Input Data

Number of MPP trackers2
Maximum PV input power10,3 kW
Feed-in start voltage (Udc start)
80 V
Nominal input voltage (Udc,r)
610 V
Min. MPP voltage (Umpp min)246 V
Max. MPP voltage (Umpp max)800 V

Output Data

AC nominal output (Pac,r)
9999 W
Max. output power (Pac max)
9999 VA
Max. grid power demand9999 VA
Max. AC output current18,5 A
Grid connection (Uac,r)
3~NPE 400/230, 3~NPE 380/220 V
AC voltage range (Umin - Umax)
154 - 280 V
Frequency (fr)
50 / 60 Hz
Frequency range (fmin - fmax)
45 - 66 Hz
Power factor (cos φac,r)
0,7-1 ind./cap.
Back-up power1~NPE 220V / 230V
Nominal AC output current (380VAC)12,1 A
Nominal AC output current (400VAC)11,6 A

Output Data PV Point

Max continuous output power3000 VA
Nom. output current (Iac max)
13 A
Grid connection1 ~ NPE 220 V / 230 V
Frequency53 Hz / 63 Hz
Max. switchover time PV-Point15 s
Frequency in backup power mode53 Hz

Battery Connection

Max. input current (Idc max.)
22 A
Min. DC input voltage160 V
Max. DC input voltage531 V
Min. DC input voltage Battery input160 V
Max. DC input voltage Battery input700 V

General Data

Dimension / length180 mm
Dimension / width529 mm
Dimension / height595 mm
Dimension / depth180 mm
Weight24,27 kg
Weight22,75 kg
Weight incl. packaging28 kg
Degree of protectionIP66
Night-time consumption<10 W
Inverter designTransformerless
CoolingRegulated air cooling
InstallationIndoor and outdoor installation
Ambient temperature range-25°C - +60°C
Permitted humidity0 - 100 %
Max. altitude3 000 m / 4 000 m
Max. altitude 2)
4000 m
DC PV connection technology3x DC+ and 3x DC- push-in spring terminals 2.5 - 10 mm²
AC connection technology5 pole AC push-in spring terminals 1.5 - 10 mm²
3 pole backup power push-in spring terminals 1.5mm² - 10mm²
5x PE-screw terminals 2.5 - 16 mm²
Certificates and compliance with standardsEC 62109, IEC 62116, IEC 61727, IEC 62909, VDE 0126,
VDE AR-N4105, AS/NZS 4777.2, EN 50549, CEI 0-21, G98/G99, R25​
AC connection technologyPV Point

Efficiency

Max. efficiency (PV - grid)98,3 %
European efficiency (ηEU)97.0 / 98.1 / 97.9 (246Vdc / 610Vdc / 800Vdc)
η at 5% Pac,r 3)
93.0 / 95.8 / 95.0 (246Vdc / 610Vdc / 800Vdc)
η at 10% Pac,r 3)
95.6 / 97.4 / 96.9 (246Vdc / 610Vdc / 800Vdc)
η at 20% Pac,r 3)
96.8 / 98.1 / 97.8 (246Vdc / 610Vdc / 800Vdc)
η at 25% Pac,r 3)
97.1 / 98.2 / 98.0 (246Vdc / 610Vdc / 800Vdc)
η at 30% Pac,r 3)
97.3 / 98.3 / 98.1 (246Vdc / 610Vdc / 800Vdc)
η at 50% Pac,r 3)
97.4 / 98.3 / 98.1 (246Vdc / 610Vdc / 800Vdc)
η at 75% Pac,r 3)
97.3 / 98.2 / 98.0 (246Vdc / 610Vdc / 800Vdc)
η at 100% Pac,r 3)
97.0 / 98.0 / 97.9 (246Vdc / 610Vdc / 800Vdc)

Protection Devices

DC insulation measurementYes
Overload behaviourOperating point shift, Power limitation
DC disconnectorYes
DC Reverse polarity protectionYes

Interfaces

WLAN / 2x Ethernet LANFronius Solar.web, Modbus TCP SunSpec, Fronius Solar API (JSON)
6x digital in/out + 6x digital inInterface to ripple control receiver, energy management
Emergency stop (WSD)Yes
Datalogger and web serverIncluded
2x RS485Modbus RTU SunSpec (third-party supplier) / Fronius Smart Meter, battery, Fronius Ohmpilot
The hybrid functions battery connection and full backup can be retrofitted to the GEN24 by Fronius UP.storage*!

*Fronius UP.storage can only be implemented in countries with Fronius Webshop. You can find an overview here.

More information about the features & availability of this product
Clear HTML version of the operating instructions. Mobile and optimised  for every device.
Information for installation and commissioning

Downloads

    Show all downloads for product