Symo Advanced

Please choose your desired product.

Technical Data

Input Data

Number of MPP trackers2
Max. usable input currentNA
Max. usable input current total (MPPT1 + MPPT2)
51 A
Max. array short circuit current (1.5 * Imax)76,5 A
DC input voltage range (Udc min - Udc max)
200-1000 V
MPP Voltage Range
350-800 V
Max. input voltage (Udc max)
1000 V

Output Data

Max. output power 480 V15 kW
Max. output power 277 V15 kW
Max. output power 240 VNA
Max. output power 208 VNA
Output configuration
3~ NPE 480 V
Frequency range50-66 Hz
Frequency60 Hz
Power factor range
0-1 ind./cap.
Max continuous output current 480 V18 A
Max. continuous output current 277 V18 A
Max. continuous output current 240 VNA
Max. continuous output current 208 VNA

General Data

Dimension / length226 mm
Dimension / width511 mm
Dimension / height724 mm
Dimension / depth226 mm
Weight43,4 kg
InstallationIndoor and outdoor installation, tilt from 0 - 90 degrees (Fronius Shade Cover required for installation angles less than 15 degrees)
Permitted humidity0 - 100 % (non-condensing)
Degree of protectionNEMA 4X
Night-time consumption<1 W
Inverter designTransformerless
CoolingVariable speed fan
Ambient Temperature Range-40°F - + 140°F (-40°C - +60°C)
Max. altitude2000 m (6562 ft) with a max. input voltage of 1000 V / 3400 m (11155 ft) with a max. input voltage of 850 V
Certificates and compliance with standardsUL 1741-2010 Second Edition (incl. UL1741 Supplement SA 2016-09 for California Rule 21), UL1998 (for functions: AFCI, RCMU and isolation monitoring), IEEE 1547-2003, IEEE 1547a-2014, IEEE 1547.1-2003, ANSI/IEEE C62.41, FCC Part 15 A & B, NEC 2017 Article 690, C22. 2 No. 107.1-16, UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013
DC connection technology6x DC+ and 6x DC- screw terminals for copper (solid / stranded / fine stranded) or aluminum (solid / stranded)
AC connection technologyScrew terminals 14-6 AWG
Interference emission classB

Protection Devices

DC reverse polarity protectionYes
Anti islandingInternal in accordance with UL 1741-2010, IEEE 1547-2003 and NEC
Over temperature protectionOutput power derating /Active cooling
AFCIYes
Rapid shutdown compliantYes
Ground fault protection with isolation monitor interrupterYes
DC disconnectorYes

Interfaces

Compatible Module Level ElectronicTigo TS4-F based on SunSpec PLC (pending testing)
Power Line Communication (PLC)Yes – SunSpec Rapid Shutdown communication standard
USB (type A socket)Datalogging and inverter update possible via USB
2x RS422 (RJ45 socket)Fronius Solar Net, interface protocol
Wi-Fi / Ethernet / Serial / Datalogger and webserverWireless standard 802.11 b/g/n / Fronius Solar.web, SunSpec Modbus TCP, JSON / SunSpec Modbus RTU
6 inputs and 4 digital I/OsLoad management signaling, multipurpose I/O