Symo Advanced

Please choose your desired product.

Technical Data

Input Data

Number of MPP trackers2
Max. input current (Idc max)
33,0 / 27,0 A
Max. short circuit current, module array*
68,0 / 55,7 A
DC input voltage range (Udc min - Udc max)
200 - 1000 V
Feed-in start voltage (Udc start)
200 V
Nominal input voltage (Udc,r)
600 V
MPP voltage range (Umpp min - Umpp max)
370 - 800 V
Usable MPP voltage range200 - 800 V
Number of DC connections3 + 3
Max. PV generator power (Pdc max
26,3 kWpeak

Output Data

AC nominal output (Pac,r)
17,5 kW
Max. output power (Pac max)
17,5 kVA
AC output current (Iac nom)
25,3 A
Grid connection (Uac,r)
3~NPE 400/230, 3~NPE 380/220 V
AC voltage range (Umin - Umax)
150 - 280 V
Frequency (fr)
50 / 60 Hz
Frequency range (fmin - fmax)
45 - 65 Hz
Power factor (cos φac,r)
0 - 1 ind./cap.

General Data

Dimension / length225 mm
Dimension / width510 mm
Dimension / height725 mm
Dimension / depth225 mm
Weight39,8 kg
Weight incl. packaging46,2 kg
Degree of protectionIP 66
Protection class1
Overvoltage category (DC / AC) 1)
2 / 3
Night-time consumption<1 W
CoolingRegulated air cooling
InstallationIndoor and outdoor installation
Ambient temperature range-25°C - +60°C
Permitted humidity0 - 100 %
Max. altitude 2)
3400 m
DC connection technology6x DC+ and 6x DC- screw terminals 2.5 - 16 mm²
AC connection technology5-pin AC screw terminals 2.5 - 16 mm²
Certificates and compliance with standardsIEC 62109-1/-2, IEC 62116, IEC 61727, VDE 0126-1-1/A1, VDE AR-N 4105, G98/1, G99/1, AS/NZS 4777.2, UNE 206007-1, CEI 0-21, CEI 0-16, NRS 097-2-1, TOR Erzeuger Typ A, VDE AR-N 4110, EN 50549-1/-2, IEC 61683, IEC60068, IEC 63027:2023
Interference emission classB

Efficiency

Max. efficiency (PV - grid)97,9 %
European efficiency (ηEU)96.5 / 97.6 / 97.1%
η at 5% Pac,r 3)
92.7 / 94.5 / /91.8&
η at 10% Pac,r 3)
94.8 / 96.5 / 95.2%
η at 20% Pac,r 3)
96.3 / 97.5 / 96.8%
η at 25% Pac,r 3)
96.5 / 97.7 / 97.0%
η at 30% Pac,r 3)
96.7 / 97.8 / 97.2%
η at 50% Pac,r 3)
96.8 / 97.9 / 97.5%
η at 75% Pac,r 3)
96.7 / 97.9 / 97.6%
η at 100% Pac,r 3)
96.6 / 97.8 / 97.5%
MPP adaptation efficiency>99.9%

Protection Devices

DC insulation measurementYes
Overload behaviourOperating point shift. Power limitation
DC disconnectorYes
DC Reverse polarity protectionYes
Arc fault circuit interrupter (Fronius Arc Guard)Yes

Interfaces

Wi-Fi / Ethernet LANFronius Solar.web, Modbus TCP SunSpec, Fronius Solar API (JSON)
6 inputs and 4 digital I/OsInterface to ripple control receiver, energy management
USB (type A socket) 4)
Data logging, inverter update via USB flash drive

2 × RS422 (RJ45 socket) 4)

Fronius Solar Net
Signalling output 4)
Energy management (floating relay output)
Datalogger and web serverIncluded
External input 4)
S0 meter connection / Evaluation of overvoltage protection
RS485Modbus RTU SunSpec or meter connection