Symo

Please choose your desired product.

Technical Data

Input Data

Number of MPP trackers2
Max. input current (Idc max)
16,0 / 16,0 A
Max. short circuit current, module array*
31 / 31 A
DC input voltage range (Udc min - Udc max)
150 - 1000 V
Feed-in start voltage (Udc start)
200 V
Nominal input voltage (Udc,r)
595 V
MPP voltage range (Umpp min - Umpp max)
150 - 800 V
Usable MPP voltage range150 - 800 V
Number of DC connections2 + 2
Max. PV generator power (Pdc max
7,4 kWpeak

Output Data

AC nominal output (Pac,r)
3700 W
Max. output power (Pac max)
3700 VA
AC output current (Iac nom)
5,3 A
Grid connection (Uac,r)
3~ NPE 400/230, 3~ NPE 380/220 V
AC voltage range (Umin - Umax)
150 - 280 V
Frequency (fr)
50 / 60 Hz
Frequency range (fmin - fmax)
45 - 65 Hz
Power factor (cos φac,r)
0,85 - 1 ind./cap.

General Data

Dimension / length205,5 mm
Dimension / width432,5 mm
Dimension / height642,5 mm
Dimension / depth205,5 mm
Weight19,75 kg
Weight incl. packaging23,05 kg
Degree of protectionIP 65
Protection class1
Overvoltage category (DC / AC) 1)
2 / 3
Night-time consumption< 1 W
Inverter designTransformerless
CoolingRegulated air cooling
InstallationIndoors and outdoors
Ambient temperature range-25°C - +60°C
Permitted humidity0 - 100 %
Max. altitude 2)
3400 m
DC connection technology4x DC+ and 4x DC- screw terminals 2.5 - 16 mm² (16 mm² without ferrules)
AC connection technology5-pin AC screw terminals 2.5 - 16 mm² (16 mm² without ferrules)
Certificates and compliance with standardsÖVE / ÖNORM E 8001-4-712, DIN V VDE 0126-1-1/A1, VDE AR N 4105, IEC 62109-1/-2, IEC 62116, IEC 61727, AS 3100,
AS 4777-2, AS 4777-3, CER 06-190, G83/2, UNE 206007-1, SI 4777, CEI 0-21, NRS 097
Sound emissions52,6 dB(A)
Interference emission classB

Efficiency

Max. efficiency (PV - grid)98 %
European efficiency (ηEU)96,9 %
η at 5% Pac,r 3)
81,6 / 87,8 / 82,8 %
η at 10% Pac,r 3)
87,9 / 93,6 / 90,5 %
η at 20% Pac,r 3)
91,9 / 96,0 / 94,1 %
η at 25% Pac,r 3)
92,9 / 96,6 / 95,2 %
η at 30% Pac,r 3)
93,5 / 97,0 / 95,8 %
η at 50% Pac,r 3)
94,6 / 97,7 / 96,8 %
η at 75% Pac,r 3)
95,0 / 97,9 / 97,4 %
η at 100% Pac,r 3)
95,1 / 98,0 / 97,5 %
MPP adaptation efficiency> 99,9 %

Protection Devices

DC insulation measurementYes
Overload behaviourOperating point shift, power limitation
DC disconnectorYes
DC Reverse polarity protectionYes

Interfaces

Wi-Fi / Ethernet LANFronius Solar.web, Modbus TCP SunSpec, Fronius Solar API (JSON)
6 inputs and 4 digital I/OsInterface to ripple control receiver
USB (type A socket) 4)
Data logging, inverter update via USB flash drive

2 × RS422 (RJ45 socket) 4)

Fronius Solar Net
Signalling output 4)
Energy management (floating relay output)
Datalogger and web serverIntegrated
External input 4)
S0 meter connection / Evaluation of overvoltage protection
RS485Modbus RTU SunSpec or meter connection
Help with installing and using this product.

Downloads

    Show all downloads for product
    Smart Grid Ready
    1 / 3
    Fronius SnapINverter with innovative hinged system
    Solutions for the home
    Smart Grid Ready

    Footnotes for technical data 

    1) According to IEC 62109-1.

    2) Unrestricted/restricted voltage range.

    3) And at Umpp min / Udc,r / Umpp max.

    4) Also available in the light version.

     

    * Isc pv = Isc max ≥ Isc (STC) x 1,25 according to e.g.: IEC 60364-7-712, NEC 2020, AS/NZS 5033:2021.