Primo GEN24 Plus

Please choose your desired product.

Technical Data

Input Data

Number of MPP trackers2
Max. input current (Idc max)
22 / 22 A
Max. short circuit current, module array*
41,25 / 36 A
DC input voltage range (Udc min - Udc max)
65 - 600 V
Feed-in start voltage (Udc start)
80 V
Nominal input voltage (Udc,r)
400 V
MPP voltage range (Umpp min - Umpp max)
260 - 480 V
Usable MPP voltage range65 - 480 V
Number of DC connections2+2
Max. PV generator power (Pdc max
15 kWpeak

Output Data

AC nominal output (Pac,r)
10 kW
Max. output power (Pac max)
10 kVA
Max. AC output current45,45 A
Grid connection (Uac,r)
1~ NPE 220/230 V
AC voltage range (Umin - Umax)
155 - 270 V
Frequency (fr)
50 / 60 Hz
Frequency range (fmin - fmax)
45 - 65 Hz
Power factor (cos φac,r)
0,8 - 1 ind./cap.

Output Data PV Point

Max continuous output power3000 VA
Nom. output current (Iac max)
13 A
Max. switchover time PV-Point20 s
Frequency in backup power mode53 Hz

Battery Connection

Max. input current (Idc max.)
22 A
DC input voltage range (Udc min - Udc max)
150 V - 455 V 7)
Max. input / output power (Depending on the connected battery)10,36 kW
Min. DC input voltage150 V
Max. DC input voltage455 V

General Data

Dimension / width529 mm
Dimension / height595 mm
Dimension / depth180 mm
Weight21 kg
Weight incl. packaging26,05 kg
Degree of protectionIP66
Protection class1
Overvoltage category (DC / AC) 1)
2 / 3
Night-time consumption9 W
Inverter designTransformerless
CoolingRegulated air cooling
InstallationIndoor and outdoor installation
Ambient temperature range-40°C - +60°C
Permitted humidity0 - 100 %
Max. altitude 2)
4000 m
DC PV connection technology4x DC+ and 4x DC- push-in spring terminals 2.5 - 10 mm²
DC battery connection technology1x BATT+ and 1x BATT- push-in spring terminals 2.5 - 10 mm²
AC connection technology3 pole AC push-in spring terminals 2.5 - 10 mm²
3 pole backup power push-in spring terminals 1.5mm² - 10mm²
2x PE-screw terminals 2.5 - 16 mm² and  3x 2,5 - 10mm²
Back-up power functionsPV Point, Full Backup 4)
Compatible batteriesBYD Battery-Box Premium HVS/HVM  & LG RESU FLEX 5)
Sound emissions51 dB(A)
Interference emission classB

Efficiency

Max. efficiency (PV - grid)97,3 %
European efficiency (ηEU)96.6 / 97.0 / 96.5 (260Vdc / 400Vdc / 480Vdc)
η at 5% Pac,r 3)
91.9 / 92.7 / 90.8 (260Vdc / 400Vdc / 480Vdc)
η at 10% Pac,r 3)
95.2 / 95.7 / 94.6 (260Vdc / 400Vdc / 480Vdc)
η at 20% Pac,r 3)
96.6 / 97.0 / 96.4 (260Vdc / 400Vdc / 480Vdc)
η at 25% Pac,r 3)
96.9 / 97.2 / 96.7 (260Vdc / 400Vdc / 480Vdc)
η at 30% Pac,r 3)
96.9 / 97.2 / 96.8 (260Vdc / 400Vdc / 480Vdc)
η at 50% Pac,r 3)
97.0 / 97.3 / 97.0 (260Vdc / 400Vdc / 480Vdc)
η at 75% Pac,r 3)
96.8 / 97.2 / 97.0 (260Vdc / 400Vdc / 480Vdc)
η at 100% Pac,r 3)
96.5 / 97.0 / 96.7 (260Vdc / 400Vdc / 480Vdc)
MPP adaptation efficiency99,74

Protection Devices

DC insulation measurementYes
Overload behaviourOperating point shift. Power limitation
DC disconnectorYes
DC Reverse polarity protectionYes

Interfaces

WLAN / 2x Ethernet LANFronius Solar.web, Modbus TCP SunSpec, Fronius Solar API (JSON)
6x digital in/out + 6x digital inInterface to ripple control receiver, energy management
Emergency stop (WSD)Yes
Datalogger and web serverIncluded
2x RS485Modbus RTU SunSpec (third-party supplier) / Fronius Smart Meter, battery, Fronius Ohmpilot
More information about the features of this product
Clear HTML version of the operating instructions. Mobile and optimised  for every device.
Information for installation and commissioning

Downloads

    Show all downloads for product

    Footnotes for technical data

    1) According to IEC 62109-1. Option to retrofit surge protection device DC SPD type 1+2 for 2 MPP trackers available under the following item number: 4,240,313,CK 

    2) Unrestricted voltage range.

    3) At Umpp min. / Udc,r / Umpp max.

    4) Depending on the connected battery.

    5) This does not apply to the BYD Battery-Box Premium HVS 10.2, HVS 12.8, HVM 8.3, HVM 22.1 & LG RESU FLEX 17.2

    6) Depending on the country-specific certification and availability

    7) An AC power derating of the inverter occurs from a battery DC input voltage of 419.7 V

    8) You can find the current certificates under www.fronius.com/primo-gen24-plus-cert 

     

    * Isc pv = Isc max ≥ Isc (STC) x 1,25 according to e.g.: IEC 60364-7-712, NEC 2020, AS/NZS 5033:2021.