Primo GEN24 Plus
Please choose your desired product.
Technical Data
Input Data
| Number of MPP trackers | 2 |
|---|---|
Max. input current (Idc max) | 22 / 12 A |
Max. short circuit current, module array* | 41,25 / 22 A |
DC input voltage range (Udc min - Udc max) | 65 - 600 V |
Feed-in start voltage (Udc start) | 80 V |
Nominal input voltage (Udc,r) | 400 V |
MPP voltage range (Umpp min - Umpp max) | 210 - 530 V |
| Usable MPP voltage range | 65 - 530 V |
| Number of DC connections | 2+2 |
| Min. MPP voltage (Umpp min) | 210 V |
| Max. MPP voltage (Umpp max) | 530 V |
Max. PV generator power (Pdc max) | 6 kWpeak |
Output Data
AC nominal output (Pac,r) | 4000 W |
|---|---|
Max. output power (Pac max) | 4000 VA |
| Max. grid power demand | 4000 VA |
| Max. AC output current | 25,8 A |
Grid connection (Uac,r) | 1~ NPE 220/230 V |
AC voltage range (Umin - Umax) | 155 - 270 V |
Frequency (fr) | 50 / 60 Hz |
Frequency range (fmin - fmax) | 45 - 65 Hz |
Power factor (cos φac,r) | 0,8 - 1 ind./cap. |
| Back-up power | 1~NPE 220 V / 230 V |
| Nom. output current (220VAC) | 18,2 A |
| Nom. output current (230VAC) | 17,4 A |
Output Data PV Point
| Max continuous output power | 3000 VA |
|---|---|
Nom. output current (Iac max) | 13 A |
| Grid connection | 1 ~ NPE 220 V / 230 V |
| Frequency | 50 Hz / 60 Hz |
| Max. switchover time PV-Point | 15 s |
| Max. switchover time Full Backup | 10 s |
| Frequency in backup power mode | 53 Hz |
Battery Connection
| Number of DC connections | 1 |
|---|---|
Max. input current (Idc max.) | 22 A |
DC input voltage range (Udc min - Udc max) | 150 V - 455 V 7) |
| Max. input / output power (Depending on the connected battery) | 4140 W |
| Max. AC charging power (Depending on the connected battery) | 4,000 W |
| Min. DC input voltage | 150 V |
| Max. DC input voltage | 455 V |
General Data
| Dimension / length | 165 mm |
|---|---|
| Dimension / width | 474 mm |
| Dimension / height | 530 mm |
| Dimension / depth | 165 mm |
| Weight | 15,38 kg |
| Weight incl. packaging | 19 kg |
| Degree of protection | IP66 |
| Protection class | 1 |
Overvoltage category (DC / AC) 1) | 2 / 3 |
| Night-time consumption | <10W |
| Inverter design | Transformerless |
| Cooling | Regulated air cooling |
| Installation | Indoor and outdoor installation |
| Ambient temperature range | -40°C - +60°C |
| Permitted humidity | 0 - 100 % |
Max. altitude 2) | 4000 m |
| DC PV connection technology | 4x DC+ and 4x DC- push-in spring terminals 2.5 - 10 mm² |
| DC battery connection technology | 1x BATT+ and 1x BATT- push-in spring terminals 2.5 - 10 mm² |
| AC connection technology | 3 pole AC push-in spring terminals 2.5 - 10 mm² 3 pole backup power push-in spring terminals 1.5mm² - 10mm² 2x PE-screw terminals 2.5 - 16 mm² and 3x 2,5 - 10mm² |
| Certificates and compliance with standards | IEC 62109, IEC 62909, AS/NZS 4777.2, CEI 0-21, ABNT BNR 16149 and 16150, IEC 62116, IEC 61727 8) |
| Back-up power functions | PV Point, full backup 4) |
| Compatible batteries | BYD Battery-Box Premium HVS/HVM & LG FLEX 5) |
| Sound emissions | 42 dB(A) |
| Interference emission class | B |
Efficiency
| Max. efficiency (PV - grid) | 97,6 % |
|---|---|
| European efficiency (ηEU) | 95.8 / 97.1 / 96.5 (210Vdc / 400Vdc / 530Vdc) |
η at 5% Pac,r 3) | 85.8 / 90.5 / 88.2 (210Vdc / 400Vdc / 530Vdc) |
η at 10% Pac,r 3) | 90.3 / 93.7 / 92.2 (210Vdc / 400Vdc / 530Vdc) |
η at 20% Pac,r 3) | 94.4 / 96.3 / 95.6 (210Vdc / 400Vdc / 530Vdc) |
η at 25% Pac,r 3) | 95.1 / 96.7 / 96.1 (210Vdc / 400Vdc / 530Vdc) |
η at 30% Pac,r 3) | 95.6 / 97.0 / 96.5 (210Vdc / 400Vdc / 530Vdc) |
η at 50% Pac,r 3) | 96.5 / 97.4 / 97.1 (210Vdc / 400Vdc / 530Vdc) |
η at 75% Pac,r 3) | 96.7 / 97.5 / 97.3 (210Vdc / 400Vdc / 530Vdc) |
η at 100% Pac,r 3) | 96.7 / 97.5 / 97.3 (210Vdc / 400Vdc / 530Vdc) |
| MPP adaptation efficiency | 99.9 |
Protection Devices
| DC insulation measurement | Yes |
|---|---|
| Overload behaviour | Operating point shift. Power limitation |
| DC disconnector | Yes |
| DC Reverse polarity protection | Yes |
Interfaces
| WLAN / 2x Ethernet LAN | Fronius Solar.web, Modbus TCP SunSpec, Fronius Solar API (JSON) |
|---|---|
| 6x digital in/out + 6x digital in | Interface to ripple control receiver, energy management |
| Emergency stop (WSD) | Yes |
| Datalogger and web server | Included |
| 2x RS485 | Modbus RTU SunSpec (third-party supplier) / Fronius Smart Meter, battery, Fronius Ohmpilot |
Downloads
Footnotes for technical data
1) According to IEC 62109-1. Option to retrofit surge protection device DC SPD type 1+2 for 2 MPP trackers available under the following item number: 4,240,313,CK
2) Unrestricted voltage range.
3) At Umpp min. / Udc,r / Umpp max.
4) Depending on the connected battery.
5) This does not apply to the BYD Battery-Box Premium HVS 10.2, HVS 12.8, HVM 8.3, HVM 22.1 & LG RESU FLEX 17.2
6) Depending on the country-specific certification and availability
7) An AC power derating of the inverter occurs from a battery DC input voltage of 419.7 V
8) You can find the current certificates under www.fronius.com/primo-gen24-plus-cert
* Isc pv = Isc max ≥ Isc (STC) x 1,25 according to e.g.: IEC 60364-7-712, NEC 2020, AS/NZS 5033:2021.