Primo GEN24

Please choose your desired product.

Technical Data

Input Data

Number of MPP trackers2
Max. input current (Idc max)
22 / 12 A
Max. short circuit current, module array*
41,25 / 22 A
DC input voltage range (Udc min - Udc max)
65 - 600 V
Feed-in start voltage (Udc start)
80 V
Nominal input voltage (Udc,r)
400 V
MPP voltage range (Umpp min - Umpp max)
230 - 480 V
Usable MPP voltage range65 - 480 V
Number of DC connections2+2
Max. PV generator power (Pdc max
9 kWpeak

Output Data

AC nominal output (Pac,r)
6000 W
Max. output power (Pac max)
6000 VA
Max. grid power demand6000 VA
Max. AC output current27,5 A
Grid connection (Uac,r)
1~ NPE 220/230 V
AC voltage range (Umin - Umax)
155 - 270 V
Frequency (fr)
50 / 60 Hz
Frequency range (fmin - fmax)
45 - 65 Hz
Power factor (cos φac,r)
0,8 - 1 ind./cap.
Back-up power1~NPE 220 V / 230 V
Nom. output current (220VAC)27.3 A
Nom. output current (230VAC)26.1 A

Output Data PV Point

Max continuous output power3000 VA
Nom. output current (Iac max)
13 A
Grid connection1~NPE 220 V / 230 V
Frequency50 Hz / 60 Hz
Max. switchover time PV-Point15 s
Frequency in backup power mode53 Hz

General Data

Dimension / length165 mm
Dimension / width474 mm
Dimension / height530 mm
Dimension / depth165 mm
Weight15,38 kg
Weight incl. packaging19 kg
Degree of protectionIP66
Protection class1
Overvoltage category (DC / AC) 1)
2 / 3
Night-time consumption< 10 W
Inverter designTrafolos
CoolingRegulated air cooling
InstallationIndoor and outdoor installation
Ambient temperature range-40°C - +60°C
Permitted humidity0 - 100 %
Max. altitude 2)
4000 m
DC PV connection technology4x DC+ and 4x DC- push-in spring-loaded terminals 2.5 - 10 mm²
AC connection technology3-pole AC push-in spring-loaded terminals 2.5 - 10 mm²
3-pole backup power push-in spring-loaded terminals 1.5 mm² - 10 mm²
2x PE screw terminals 2.5 - 16 mm² and 3x 2.5 - 10 mm²
Certificates and compliance with standardsIEC 62109, IEC 62909, AS/NZS 4777.2, CEI 0-21, ABNT BNR 16149 and 16150, IEC 62116, IEC 61727,G98/G994)
Back-up power functionsPV Point
Sound emissions42 dB(A)
Interference emission classB

Efficiency

Max. efficiency (PV - grid)97,6 %
European efficiency (ηEU)96.1 / 97.1 / 96.7 (230Vdc / 400Vdc / 480Vdc)
η at 5% Pac,r 3)
88.4 / 92.1 / 90.2 (230Vdc / 400Vdc / 480Vdc)
η at 10% Pac,r 3)
93.3 / 95.5 / 94.6 (230Vdc / 400Vdc / 480Vdc)
η at 20% Pac,r 3)
95.8 / 97.0 / 96.5 (230Vdc / 400Vdc / 480Vdc)
η at 25% Pac,r 3)
96.2 / 97.2 / 96.8 (230Vdc / 400Vdc / 480Vdc)
η at 30% Pac,r 3)
96.5 / 97.4 / 97.0 (230Vdc / 400Vdc / 480Vdc)
η at 50% Pac,r 3)
96.8 / 97.5 / 97.3 (230Vdc / 400Vdc / 480Vdc)
η at 75% Pac,r 3)
96.8 / 97.5 / 97.3 (230Vdc / 400Vdc / 480Vdc)
η at 100% Pac,r 3)
96.7 / 97.4 / 97.1 (230Vdc / 400Vdc / 480Vdc)
MPP adaptation efficiency99.9

Protection Devices

DC insulation measurementYes
Overload behaviourOperating point shift, power limitation
DC disconnectorYes
DC Reverse polarity protectionYes

Interfaces

WLAN / 2x Ethernet LANFronius Solar.web, Modbus TCP SunSpec, Fronius Solar API (JSON)
6x digital in/out + 6x digital inConnection to ripple control receivers, energy management
Emergency stop (WSD)Yes
Datalogger and web serverIntegrated
2x RS485Modbus RTU SunSpec (third-party provider) / Fronius Smart Meter, battery, Fronius Ohmpilot
Overview of advantages, features, and possible applications.
Help with installing and using this product.

Frequently searched downloads

    Show all downloads for product

    Downloads

      Show all downloads for product

      Footnotes for technical data

      1) According to IEC 62109-1. Option to retrofit surge protection device DC SPD type 1+2 for 2 MPP trackers available under the following item number: 4,240,313,CK 

      2) Unrestricted voltage range.

      3) At Umpp min. / Udc,r / Umpp max.

      4) You can find the current certificates under www.fronius.com/primo-gen24-plus-cert 

       

      * Isc pv = Isc max ≥ Isc (STC) x 1,25 according to e.g.: IEC 60364-7-712, NEC 2020, AS/NZS 5033:2021.