Digital Operating Instruction
Clear HTML version of the operating instructions. Mobile and optimised for every device.
Width | 429 mm |
---|---|
Height | 627 mm |
Depth | 206 mm |
Weight | 21,5 kg |
Dimension (width) | 429 mm |
Dimension (height) | 627 mm |
Dimension (depth) | 206 mm |
Weight | 21,5 kg |
Protection class | NEMA 4X |
Night time consumption | < 1 W |
Inverter topology | Transformerless |
Cooling | Variable speed fan |
Elevation | 4000 m (13120 ft) with a max. input voltage of 1000 V |
Certificates and compliance with standards | UL 1741-2010 Second Edition (incl. UL1741 Supplement SA 2016-09 for California Rule 21 and Hawaiian Electric Code Rule 14H), UL1998 (for functions: AFCI, RCMU and isolation monitoring), IEEE 1547-2003, IEEE 1547.1-2003, ANSI/IEEE C62.41, FCC Part 15 A & B, NEC 2017 Article 690, C22. 2 No. 107.1-16, UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 – 2013 |
DC connection terminals | 4x DC+ and 4x DC- screw terminals for copper (solid/stranded/fine stranded) or aluminium (solid/stranded) |
AC connection terminals | Screw terminals 12 - 6 AWG |
Revenue Grade Metering | Optional (ANSI C12.1 accuracy) |
UL safety standards & network regulations | UL 1741-2010, UL 1998, UL 1699B Issue 2-2013 |
Number of MPPT | 2 |
---|---|
Recommended PV Power (kWp) | 6,6 - 12,7 kWp |
Max. usable input current | 18,0 / 18,0 A |
Max. usable input current total (MPPT1 + MPPT2) | 36 A |
Max. array short circuit current (1.5 * Imax) | 27 / 27 A |
Nominal input voltage | 420 V |
Operating voltage range | 80 - 1000 V |
MPP Voltage Range | 270 - 800 V |
Max. input voltage (Udc max) | 1000 V |
Max. output power 240 V | 8200 VA |
---|---|
Max. output power 208 V | 7900 VA |
Output configuration | 1~ NPE 208 / 240 V |
Frequency range | 45 - 66 Hz |
Nominal operating frequency | 60 Hz |
Total harmonic distortion | < 5 % |
Power factor range | 0,85 - 1 ind,/cap, |
Max. continuous output current 240 V | 34,2 A |
Max. continuous output current 208 V | 38,0 A |
OCPD/AC breaker size 208 V | 50 A |
Max. efficiency | 97 % |
CEC efficiency 240 V | 96,5 % |
CEC efficiency 208 V | 96,5 % |
DC reverse polarity protection | Yes |
---|---|
Anti islanding | internal; in accordance with UL 1741-2016-09, IEEE 1547-2003 and NEC 2017 |
Over temperature protection | Output power derating / Active cooling |
AFCI | Yes |
Rapid shutdown compliant | Yes (according to NEC 2014) |
Ground fault protection with isolation monitor interrupter | Yes |
DC disconnect | Yes |
Wi-Fi / Ethernet LAN | Wireless standard 802.1 1 b/g/n / Fronius Solar.web, SunSpec Modbus TCP, JSON |
---|---|
USB (type A socket) | Datalogging and inverter update possible via USB |
2x RS422 (RJ45 socket) | Fronius Solar Net |
Datalogger and webserver | Included |
Serial RS485 | SunSpec Modbus RTU |
6 inputs and 4 digital I/Os | Load management; signaling, multipurpose I/O |
Clear HTML version of the operating instructions. Mobile and optimised for every device.
The deliberate design of the Fronius SnapINverter meets great enthusiasm of our installers and customers.