Digital Operating Instruction
Clear HTML version of the operating instructions. Mobile and optimised for every device.
Width | 511 mm |
---|---|
Height | 724 mm |
Depth | 226 mm |
Weight | 35,52 kg |
Dimension (width) | 511 mm |
Dimension (height) | 724 mm |
Dimension (depth) | 226 mm |
Weight | 35,52 kg |
Protection class | NEMA 4X |
Night time consumption | < 1 W |
Inverter topology | Transformerless |
Cooling | Variable speed fan |
Elevation | 2000 m (6560 ft) with a max. input voltage of 1000 V / 3400 m (11160 ft) with a max. input voltage of 850 V |
Certificates and compliance with standards | UL 1741-2010, UL1998 (for functions: AFCI and isolation monitoring), IEEE 1547-2003, IEEE 1547.1-2008, ANSI/IEEE C62.41, FCC Part 15 A & B, NEC Article 690, C22. 2 No. 107.1-01 ( September 2001), UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013 |
DC connection terminals | 6x DC+ and 6x DC- screw terminals for copper (solid / stranded / fine stranded) or aluminium (solid / stranded) |
AC connection terminals | Screw terminals 14-6 AWG |
UL safety standards & network regulations | UL 1741-2015, UL 1998, UL 1699B Issue 2-2013 |
Interference emission class | B |
Number of MPPT | 1 |
---|---|
Recommended PV Power (kWp) | 12,0 - 19,5 kWp |
Max. usable input current | 50,0 A |
Max. usable input current total (MPPT1 + MPPT2) | 50 A |
Max. array short circuit current (1.5 * Imax) | 75,0 A |
Nominal input voltage | 325 V |
Operating voltage range | 325 - 1000 V |
MPP Voltage Range | 325 - 850 V |
Max. input voltage (Udc max) | 1000 V |
Integrated DC string fuse holders | 6- and 6+ |
Max. output power 480 V | NA |
---|---|
Max. output power 240 V | NA |
Max. output power 208 V | 15000 VA |
Output configuration | 3~ NPE 208/220 V |
Frequency range | 45 - 65 Hz |
Nominal operating frequency | 60 Hz |
Total harmonic distortion | < 3,5 % |
Power factor range | 0 - 1 ind,/cap, |
Max continuous output current 480 V | NA |
Max. continuous output current 240 V | NA |
Max. continuous output current 208 V | 41,6 A |
OCPD/AC breaker size 480 V | NA |
OCPD/AC breaker size 208 V | 60 A |
Max. efficiency | 97,3 % |
CEC efficiency 480 V | NA |
CEC efficiency 240 V | NA |
CEC efficiency 208 V | 96,5 % |
DC reverse polarity protection | Yes |
---|---|
Anti islanding | Internal; in accordance with UL 1741-2005, IEEE 1547-2003 and NEC |
Over temperature protection | Output power derating / Active cooling |
AFCI | Yes |
Rapid shutdown compliant | Yes (according to NEC 2014) |
Ground fault protection with isolation monitor interrupter | Yes |
DC disconnect | Yes |
USB (type A socket) | Datalogging and inverter update possible via USB |
---|---|
2x RS422 (RJ45 socket) | Fronius Solar Net |
Wi-Fi / Ethernet / Serial / Datalogger and webserver | Wireless standard 802.1 1 b/g/n / Fronius Solar.web, SunSpec Modbus TCP, JSON / SunSpec Modbus RTU - Available with the Fronius Datamanager 2.0 Card only |
6 inputs and 4 digital I/Os | Load management; signaling, multipurpose I/O - Available with the Fronius Datamanager 2.0 Card only |